Inspection

Outstanding Inspections

Case Number: T04FR00723
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
12/02/2004 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 304.3.1- Spontaneous ignition. Materials susceptible to spontaneous ignition, such as oily rags, shall be stored in a listed disposal container. Contents of such containers shall be removed and disposed of daily.
12/02/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation tfc 605.3- Working space and clearance. A working space of not less than 30" in width, 36" in depth, 78" in height shall be provided in front of electrical service equipment.
12/02/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Unapproved conditions. Open junction boxes and open wiring splices shall be prohibited. (above parts room)
12/02/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation 901.6- Inspection, testing, maintenance. Fire extinguishers shall be serviced annually.
12/02/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.4- Installation. Found sprinkler head behind stock. 18" space shall be provided.
12/02/2004 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation TFC 3404.3- Containers. Storage of flammable liquids in closed containers shall be in compliance. Gas cans without caps shall be prohibited.