Case: T04FR00668

Parcel: 10409032F


Addresses:

4225 N ORACLE RD

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 Unapproved conditions - The open junction box in the sprinkler riser room shall have an approved cover.
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 A working space of 36 inches deep and 78 inches high shall be in front of electrical panels.
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3.1 Labeling - Electrical Room door shall be labled.
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.5 Extension cords shall not be used in break room as permanent wiring or extended through ceilings.
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Power cord for cooler at front of store shall not be extended under door.