Case: T04FR00668
Case Details
Entered Date:
11/22/2004
Applicant:
DETRICK SHELLEY B & BARBARA J
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00668
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2 Storage of combustible materials shall be orderly. (stockroom) |
| 11/22/2004 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.3 Equipment rooms - Combustible materials shall not be stored in equipment rooms. |
| 11/22/2004 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 510.1 Riser room door shall be labled. |
| 11/22/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Power cord for cooler at front of store shall not be extended under door. |
| 11/22/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 A working space of 36 inches deep and 78 inches high shall be in front of electrical panels. |
| 11/22/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3.1 Labeling - Electrical Room door shall be labled. |
| 11/22/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords shall not be used in break room as permanent wiring or extended through ceilings. |
| 11/22/2004 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Unapproved conditions - The open junction box in the sprinkler riser room shall have an approved cover. |
| 11/22/2004 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign illumination - Exit sign at northwest corner exit shall be lit. |
| 11/22/2004 | VIOL - HIGH PILED COMBUSTIBLES | TKNAPP | Correction Required | 2305.4 Aisle maintenance - When restocking is not being done aisles shall be kept clear. During mechanical stocking a 44 inch aisle shall be maintained. A minimum of one half the aisle width shall be maintained during restocking. Storage in stockroom shall be removed from the aisle. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00668
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2004 | INSP - FULL | TKNAPP | Approved |