Full Inspection

Outstanding Inspections

Case Number: T04FR00668
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
11/22/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2 Storage of combustible materials shall be orderly. (stockroom)
11/22/2004 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.3 Equipment rooms - Combustible materials shall not be stored in equipment rooms.
11/22/2004 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 510.1 Riser room door shall be labled.
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Power cord for cooler at front of store shall not be extended under door.
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 A working space of 36 inches deep and 78 inches high shall be in front of electrical panels.
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3.1 Labeling - Electrical Room door shall be labled.
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extension cords shall not be used in break room as permanent wiring or extended through ceilings.
11/22/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Unapproved conditions - The open junction box in the sprinkler riser room shall have an approved cover.
11/22/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign illumination - Exit sign at northwest corner exit shall be lit.
11/22/2004 VIOL - HIGH PILED COMBUSTIBLES TKNAPP Correction Required 2305.4 Aisle maintenance - When restocking is not being done aisles shall be kept clear. During mechanical stocking a 44 inch aisle shall be maintained. A minimum of one half the aisle width shall be maintained during restocking. Storage in stockroom shall be removed from the aisle.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00668
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/06/2004 INSP - FULL TKNAPP Approved