Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 11/02/2004 |
VIOL - MEANS OF EGRESS |
|
Correction Required |
1026.3 Exit sign illumination - Exit signs shall be illuminated at all times. The exit sign at the north side dining area shall be repaired. |
| 11/02/2004 |
VIOL - MEANS OF EGRESS |
|
Correction Required |
1008.1.8.3 Locks and Latches - The east side storeoom doors shall be openable without a key or special knowledge. Locks shall be changed to those that do not require a key. |
| 11/02/2004 |
VIOL - MEANS OF EGRESS |
|
Correction Required |
1008.1.8.4 Bolt Locks - The manually operated flush bolts on the east exit shall be removed. |
| 11/02/2004 |
VIOL - MEANS OF EGRESS |
|
Correction Required |
1027.3 Obstructions - The east exit shall be maintained free from obstructions. |