Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/02/2004

Applicant:

EL GRAN MEZON DEL COBRE LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00539
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
11/02/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Inspection - Portable fire extinguishers shall be inspected every year.
11/02/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.4 Extinguishing system service - The cooking hood system shall be inspected every 6 months.
11/02/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.3 Locks and Latches - The east side storeoom doors shall be openable without a key or special knowledge. Locks shall be changed to those that do not require a key.
11/02/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.4 Bolt Locks - The manually operated flush bolts on the east exit shall be removed.
11/02/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit sign illumination - Exit signs shall be illuminated at all times. The exit sign at the north side dining area shall be repaired.
11/02/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.3 Obstructions - The east exit shall be maintained free from obstructions.
11/02/2004 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 Security - The compressed gas cylinders shall be secured against accidental dislodgement.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00539
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/14/2008 INSP - FULL TKNAPP Approved