Case: T04FR00456

Parcel: 124150030


Addresses:

748 E 16TH ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
01/10/2005 VIOL - FIRE PROTECTION SYSTEMS Approved Room was removed.
Insulation was removed.
WMG repaired.
Canopies taking down.
Stock was lowered.
10/28/2004 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6 repairs. Need to repair following areas:
1.) Remove Insulation from sprinkler heads
2.) Repair or replace water motor gong
3.) Stock needs to be 18" from sprinkler heads
4.) Remove or sprinkler canopies on southside of building 2700 sq. ft.
5.) Sprinkler rear storage area just right of inspectors test valve.
Feild notice was given.
10/19/2004 VIOL - FIRE PROTECTION SYSTEMS Violation Sprinkler report received problems found
10/15/2004 VIOL - FIRE PROTECTION SYSTEMS Violation Need to submit a up to date inspection report.