Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2005 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Room was removed. Insulation was removed. WMG repaired. Canopies taking down. Stock was lowered. |
|
| 10/28/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6 repairs. Need to repair following areas: 1.) Remove Insulation from sprinkler heads 2.) Repair or replace water motor gong 3.) Stock needs to be 18" from sprinkler heads 4.) Remove or sprinkler canopies on southside of building 2700 sq. ft. 5.) Sprinkler rear storage area just right of inspectors test valve. Feild notice was given. |
|
| 10/19/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Sprinkler report received problems found | |
| 10/15/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Need to submit a up to date inspection report. |