Case: T04FR00456
Case Details
Entered Date:
10/15/2004
Applicant:
AIRCO PRODUCTS INC
Description:
Sprinkler report needed
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00456
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2004 | VIOL - FIRE PROTECTION SYSTEMS | CSCHULTZ | Approved | TFC 901.6 repairs. Need to repair following areas: 1.) Remove Insulation from sprinkler heads 2.) Repair or replace water motor gong 3.) Stock needs to be 18" from sprinkler heads 4.) Remove or sprinkler canopies on southside of building 2700 sq. ft. 5.) Sprinkler rear storage area just right of inspectors test valve. Feild notice was given. |