Inspection Status: Correction Required
Inspection History: VIOL - FLAMMABLE FINISHES
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2004 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1503.2.2 Open flames and sparks - Open flames and spark producing devices shall not be located within 20 feet of paint booth unless separated by partition. |
| 10/14/2004 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1503.2.6 Smoking - No smoking signs shall be posted near east end and near enterance door to paint booth. |
| 10/14/2004 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1503.2.7 Welding - No welding signs shall be posted near east end and near enterance door to paint booth. |
| 10/14/2004 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.6 Fire protection - Spray booths shall be protected by an approved automatic fire extinguishing system. |
| 10/14/2004 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
105.7.1 Automatic fire extinguishing systems - A permit is required to install or modify an automatic fire extinguishing system. |
| 10/14/2004 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.1.2.5 Clear Space - Spray booths shall be installed so that all parts have a clear space of 3 feet on all sides except when against a wall with a one hour rating. |
| 10/14/2004 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1503.2.1.4 Areas adjacent to spray booths - Electrical wiring located within 5 feet of spray booths shall be approved for hazardous locations. |
| 10/14/2004 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1503.2.1.4 Areas adjacent to spray booths - Electrical wiring located within 5 feet of spray booth shall be approved for hazardous locations. |