Case: T04FR00450

Parcel: 10611001H


Addresses:

3565 N ROMERO RD

Inspection Status: Correction Required

Inspection History: VIOL - FLAMMABLE FINISHES

Date Description Inspector Results Comments
10/14/2004 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.2 Open flames and sparks - Open flames and spark producing devices shall not be located within 20 feet of paint booth unless separated by partition.
10/14/2004 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.6 Smoking - No smoking signs shall be posted near east end and near enterance door to paint booth.
10/14/2004 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.7 Welding - No welding signs shall be posted near east end and near enterance door to paint booth.
10/14/2004 VIOL - FLAMMABLE FINISHES Correction Required 1504.6 Fire protection - Spray booths shall be protected by an approved automatic fire extinguishing system.
10/14/2004 VIOL - FLAMMABLE FINISHES Correction Required 105.7.1 Automatic fire extinguishing systems - A permit is required to install or modify an automatic fire extinguishing system.
10/14/2004 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.2.5 Clear Space - Spray booths shall be installed so that all parts have a clear space of 3 feet on all sides except when against a wall with a one hour rating.
10/14/2004 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.1.4 Areas adjacent to spray booths - Electrical wiring located within 5 feet of spray booths shall be approved for hazardous locations.
10/14/2004 VIOL - FLAMMABLE FINISHES Correction Required 1503.2.1.4 Areas adjacent to spray booths - Electrical wiring located within 5 feet of spray booth shall be approved for hazardous locations.