Case: T04FR00450
Case Details
Entered Date:
10/14/2004
Applicant:
KOTT DONALD E
Description:
Full Inspection
Outstanding Inspections
Case Number: T04FR00450
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2004 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Inspection - Portable fire extinguishers shall be inspected annually. Extinguishers in shop area shall be inspected. |
| 10/14/2004 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 105.7.1 Automatic fire extinguishing systems - A permit is required to install or modify an automatic fire extinguishing system. |
| 10/14/2004 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1503.2.1.4 Areas adjacent to spray booths - Electrical wiring located within 5 feet of spray booth shall be approved for hazardous locations. |
| 10/14/2004 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1503.2.1.4 Areas adjacent to spray booths - Electrical wiring located within 5 feet of spray booths shall be approved for hazardous locations. |
| 10/14/2004 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1503.2.2 Open flames and sparks - Open flames and spark producing devices shall not be located within 20 feet of paint booth unless separated by partition. |
| 10/14/2004 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1503.2.6 Smoking - No smoking signs shall be posted near east end and near enterance door to paint booth. |
| 10/14/2004 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1503.2.7 Welding - No welding signs shall be posted near east end and near enterance door to paint booth. |
| 10/14/2004 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.1.2.5 Clear Space - Spray booths shall be installed so that all parts have a clear space of 3 feet on all sides except when against a wall with a one hour rating. |
| 10/14/2004 | VIOL - FLAMMABLE FINISHES | TKNAPP | Correction Required | 1504.6 Fire protection - Spray booths shall be protected by an approved automatic fire extinguishing system. |
| 10/14/2004 | VIOL - HAZARDOUS MATERIALS,GEN | TKNAPP | Correction Required | 2703.5 Hazard Identification Signs - Visible hazard identification signs (NFPA 704) shall be posted at the enterances to the shop building. The signs shall have these ratings; Fire 3, Health 3, Reactivity 1. |
| 10/14/2004 | VIOL - FLAMMABLE LIQUIDS | TKNAPP | Correction Required | 3404.3.4.4 Liquid Storage Cabinets - Flammable/Combustible liquids in quantities over 10 gallons shall be stored in liquid storage cabinets. |
Completed Inspections
Case Status: COMPLETE
Case Number: T04FR00450
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2005 | INSP - FULL | TKNAPP | Approved |