Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/14/2004

Applicant:

KOTT DONALD E

Description:

Full Inspection

Outstanding Inspections

Case Number: T04FR00450
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
10/14/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 Inspection - Portable fire extinguishers shall be inspected annually. Extinguishers in shop area shall be inspected.
10/14/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 105.7.1 Automatic fire extinguishing systems - A permit is required to install or modify an automatic fire extinguishing system.
10/14/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.1.4 Areas adjacent to spray booths - Electrical wiring located within 5 feet of spray booth shall be approved for hazardous locations.
10/14/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.1.4 Areas adjacent to spray booths - Electrical wiring located within 5 feet of spray booths shall be approved for hazardous locations.
10/14/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.2 Open flames and sparks - Open flames and spark producing devices shall not be located within 20 feet of paint booth unless separated by partition.
10/14/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.6 Smoking - No smoking signs shall be posted near east end and near enterance door to paint booth.
10/14/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1503.2.7 Welding - No welding signs shall be posted near east end and near enterance door to paint booth.
10/14/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.1.2.5 Clear Space - Spray booths shall be installed so that all parts have a clear space of 3 feet on all sides except when against a wall with a one hour rating.
10/14/2004 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.6 Fire protection - Spray booths shall be protected by an approved automatic fire extinguishing system.
10/14/2004 VIOL - HAZARDOUS MATERIALS,GEN TKNAPP Correction Required 2703.5 Hazard Identification Signs - Visible hazard identification signs (NFPA 704) shall be posted at the enterances to the shop building. The signs shall have these ratings; Fire 3, Health 3, Reactivity 1.
10/14/2004 VIOL - FLAMMABLE LIQUIDS TKNAPP Correction Required 3404.3.4.4 Liquid Storage Cabinets - Flammable/Combustible liquids in quantities over 10 gallons shall be stored in liquid storage cabinets.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00450
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/24/2005 INSP - FULL TKNAPP Approved