Case: T04FR00368

Parcel: 13608477D


Addresses:

2475 S HARRISON RD

Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.11.6.3- Cleaning. Hoods, ducts and other components shall be free from accumulation of grease. Records of service shall be kept on site showing extent, time and date of cleaning.
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.11.6.4- Service. Automatic fire extinguishing systems shall be serviced at least every 6 months. Inspection shall be by qualified individuals and a certificate of inspection shall be forwarded to Fire Prevention,265 S Church,T/A 85701
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 904.11.6.5- Fusible link replacement. Fusible links shall be replaced at least annually.
*Placement of nozzles over woks need to be adjusted.
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 906.7- Hangers and brackets. Portable fire extinguishers shall be securely anchored in a conspicuous place.
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 906.9- Height above floor. Fire extinguishers less than 40 lbs. shall be installed no higher than 5 feet above the floor. The clearance between the bottom and the floor shall not be less than 4 inches.
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS Violation NFPA 96 11.1.2- Filter equipped exhaust system shall not be operated with filters removed.