Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.6.3- Cleaning. Hoods, ducts and other components shall be free from accumulation of grease. Records of service shall be kept on site showing extent, time and date of cleaning. | |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.6.4- Service. Automatic fire extinguishing systems shall be serviced at least every 6 months. Inspection shall be by qualified individuals and a certificate of inspection shall be forwarded to Fire Prevention,265 S Church,T/A 85701 | |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 904.11.6.5- Fusible link replacement. Fusible links shall be replaced at least annually. *Placement of nozzles over woks need to be adjusted. |
|
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 906.7- Hangers and brackets. Portable fire extinguishers shall be securely anchored in a conspicuous place. | |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 906.9- Height above floor. Fire extinguishers less than 40 lbs. shall be installed no higher than 5 feet above the floor. The clearance between the bottom and the floor shall not be less than 4 inches. | |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | Violation | NFPA 96 11.1.2- Filter equipped exhaust system shall not be operated with filters removed. |