Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/13/2004

Applicant:

WANG HAN NAI & MY MY

Description:

full inspection

Outstanding Inspections

Case Number: T04FR00368
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
09/13/2004 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 315.2- storage shall be removed from around heating devices 1. water heater in closet 2. water heater in kitchen
09/13/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Abatement of electrical hazards. Panel needs to be attached in an approved manner.
09/13/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3.1- door to electrical panels shall be plainly and visibly marked with a sign stating "ELECTRICAL ROOM".
09/13/2004 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extention cords shall not be used as permanent wiring. 1. dining room 2. outside x 2
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation NFPA 96 11.1.2- Filter equipped exhaust system shall not be operated with filters removed.
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 904.11.6.3- Cleaning. Hoods, ducts and other components shall be free from accumulation of grease. Records of service shall be kept on site showing extent, time and date of cleaning.
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 904.11.6.4- Service. Automatic fire extinguishing systems shall be serviced at least every 6 months. Inspection shall be by qualified individuals and a certificate of inspection shall be forwarded to Fire Prevention,265 S Church,T/A 85701
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 904.11.6.5- Fusible link replacement. Fusible links shall be replaced at least annually. *Placement of nozzles over woks need to be adjusted.
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Hangers and brackets. Portable fire extinguishers shall be securely anchored in a conspicuous place.
09/13/2004 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.9- Height above floor. Fire extinguishers less than 40 lbs. shall be installed no higher than 5 feet above the floor. The clearance between the bottom and the floor shall not be less than 4 inches.
09/13/2004 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1006.3- Illumination emergency power. Emergency power shall be provided for emergency lighting. 1. dining room 2. kitchen
09/13/2004 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.5.3- Power source. Exit signs shall be illuminated at all times. (dining room)