Case: T04FR00368
Case Details
Entered Date:
09/13/2004
Applicant:
WANG HAN NAI & MY MY
Description:
full inspection
Outstanding Inspections
Case Number: T04FR00368
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 09/13/2004 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2- storage shall be removed from around heating devices 1. water heater in closet 2. water heater in kitchen |
| 09/13/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Abatement of electrical hazards. Panel needs to be attached in an approved manner. |
| 09/13/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3.1- door to electrical panels shall be plainly and visibly marked with a sign stating "ELECTRICAL ROOM". |
| 09/13/2004 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extention cords shall not be used as permanent wiring. 1. dining room 2. outside x 2 |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | NFPA 96 11.1.2- Filter equipped exhaust system shall not be operated with filters removed. |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 904.11.6.3- Cleaning. Hoods, ducts and other components shall be free from accumulation of grease. Records of service shall be kept on site showing extent, time and date of cleaning. |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 904.11.6.4- Service. Automatic fire extinguishing systems shall be serviced at least every 6 months. Inspection shall be by qualified individuals and a certificate of inspection shall be forwarded to Fire Prevention,265 S Church,T/A 85701 |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 904.11.6.5- Fusible link replacement. Fusible links shall be replaced at least annually. *Placement of nozzles over woks need to be adjusted. |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Hangers and brackets. Portable fire extinguishers shall be securely anchored in a conspicuous place. |
| 09/13/2004 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.9- Height above floor. Fire extinguishers less than 40 lbs. shall be installed no higher than 5 feet above the floor. The clearance between the bottom and the floor shall not be less than 4 inches. |
| 09/13/2004 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1006.3- Illumination emergency power. Emergency power shall be provided for emergency lighting. 1. dining room 2. kitchen |
| 09/13/2004 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.5.3- Power source. Exit signs shall be illuminated at all times. (dining room) |