Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - PRECAUTION AGAINST FIRE
Case Number - T04FR00322
Inspection Description - VIOL - PRECAUTION AGAINST FIRE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2004 | VIOL - PRECAUTION AGAINST FIRE | Approved | ||
08/24/2004 | VIOL - PRECAUTION AGAINST FIRE | Violation | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. remove all storage above 18" from ceiling, with attention to east wall in west storage area TFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. |