Case: T04FR00197

Parcel: 107061090

Inspection Status: Violation

Inspection History: VIOL - HAZARDOUS MATERIALS,GEN

Date Description Inspector Results Comments
07/21/2004 VIOL - HAZARDOUS MATERIALS,GEN Violation TFC Chapter 27 & 34 HAZARDOUS MATERIALS & FLAMMABLE AND COMBUSTIBLE LIQUIDS

According to chapters 27 & 34 your maximum allowed storage for flammables liquids is 120gals per control area and 30gals open use. You have a total of 495gals on property. You do not have an approved control area to store what you have on property now. You shall remove flammable liquids to 30 gals open use only on property until an approved control area is built or approved flammable cabinets are installed, need plans and permits to make changes.