Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

07/23/2004

Applicant:

ROJO ALBERTO D & ELVA Z JT/RS

Description:

Fire Inspection

Outstanding Inspections

Case Number: T04FR00197
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
07/21/2004 COMPL - INITIAL INSPECTION CSCHULTZ Violation During an inspection for a complaint it was noticed that person was using an Illegal paint booth.
07/21/2004 VIOL - ADMINISTRATION CSCHULTZ Violation TFC 111.1 STOP WORK ORDER Order. Whenever the code official finds any work regulated by this code being performed in a manner contrary to he provisions of this code or in a dangerous or unsafe manner, the code official is authorized to issue a stop work order. Shall stop all painting in building until building is approved for such use. You will need to go to DSC and have a set of approved plans and permits to make changes.
07/21/2004 VIOL - FLAMMABLE FINISHES CSCHULTZ Violation TFC Chapter 15 FLAMMABLE FINISHES. Shall have approved spray paint booth or spray room, per Fire and Building codes.
07/21/2004 VIOL - HAZARDOUS MATERIALS,GEN CSCHULTZ Violation TFC Chapter 27 & 34 HAZARDOUS MATERIALS & FLAMMABLE AND COMBUSTIBLE LIQUIDS According to chapters 27 & 34 your maximum allowed storage for flammables liquids is 120gals per control area and 30gals open use. You have a total of 495gals on property. You do not have an approved control area to store what you have on property now. You shall remove flammable liquids to 30 gals open use only on property until an approved control area is built or approved flammable cabinets are installed, need plans and permits to make changes.
07/23/2004 INSP - FULL TKNAPP Correction Required Inspection was conducted on the main building on the property.
07/23/2004 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required Address numbers must be displayed on building. Numbers must be 12" in size.
07/23/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required Electrical hazards throughout the building. Extension cords used as permanent wiring.
07/23/2004 VIOL - WELDING & OTHER HOT WRK TKNAPP Correction Required An extinguisher should be located within 30' of hot work area.
07/23/2004 VIOL - WELDING & OTHER HOT WRK TKNAPP Correction Required Area where hot work is done should be free of combustible waste.
07/23/2004 VIOL - COMPRESSED GASES TKNAPP Correction Required Compressed gas cylinders should be secured to prevent falling.
07/23/2004 VIOL - COMPRESSED GASES TKNAPP Correction Required Compressed gas cylinders should have protective caps in place when not in use.