Permit: T04EL02318

Parcel: 125020900


Addresses:

3039 E HAWTHORNE ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/29/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode conn
THE GROUNDING SYSTEM MUST CONSIST OF ALL OF THE FOLLOWING: 1. 2-5/8'' X 8' GROUND RODS SET 6' APART IN THE AREA NEAR THE SERVICE ENTRANCE. 2. THE COLD WTR. PIPING OF THE INTERIOR OF THE HOUSE. 3. THE GAS PIPING ALSO HOUSE SIDE. LEAVE MESSAGE ON SITE INDICATING WHERE COLD WATER & GAS PIPE BONDS ARE LOCATED. THESE ITEMS ( ALL ) MUST BE ACCESSIBLE AND READILY INSPECTABLE ( W/O USING LADDER ETC) THANKS