Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 30 AMP 2 POLE 6E BREAKER NOT LISTED FOR THIS PANEL 2) CLOSED NIPPLES (BOTTOM) TO HAVE 2 LOCKNUTS ONE OUTSIDE AS WELL AS INSIDE PANEL 3) 1/2" LB TOP RH SIDE TO HAVE CLOSED NIPPLE WITH LOCK NUTS INSIDE AND OUTSIDE AND LOCK NUT OUTSIDE TO BE SEALING TYPE BECAUSE ENTRY ABOVE BUS 4) REMOVE 1" SHEET METAL SCREWS ON DEADFRONT COVER THESE CAN HARM WIRES INSIDE-USE CORRECT ONES 6) SECURE 3/4" CONDUIT RIGHT SIDE WITHIN 12" OF ENTRY 7) CLOSE UP J-BOXES ON SOUTH EXTERIOR WALL OF HOUSE AND SUPPORT 1/2" EMT NEAR GRADE 8) CLOSE J-BOX ABOVE WATER HEATER 9) WILL NEED LADDER TO ROOF TO CHECK WATER AND GAS BOND |