Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00922
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/13/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
08/11/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/PLEASE REVISE (CITY APPROVED) PLANS TO SHOW IN DETAIL THE (2) 400 AMP PANE/BOARDS AND THE LOADS FROM EACH. DESIGNATE DISCONNECTS 1,B,C,ETX? AND DESIGNATE PANEL BOARDS PERMANENTY WITH LOAD CACES. | |
08/05/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) INSTALL 3/0 ? CU. FOR GROUNDING ELECTRODE SYSTEM ON ALL DISCONNECTS OK TO TAP FOR EACH ONE 2) STRAP 4" CONDUIT 3) TAPE MARKER TO BE IN TRENCH-PRESENT ? 4) PLANS MUST BE COMPLETE AND SHOW PROPER VOLTAGE. DESCRIPTION OF PANEL TO MC INDICATOR SIMULAR, THESE PANELS ARE DIFFERENT. WHERE IS INFORMATION? |