Permit: T04EL00573

Parcel: 11903423B


Addresses:

402 W 44TH ST #01*

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/30/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
03/23/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) COLOR CODE WHITE WIRE BLACK. 2) USE PROPER FITTING TO TERMINATE LB IN PANEL, USE SEALING LOCKNUT. 3) SUPPORT 3/4 CONDUIT 3' OF TERMINATION. BOTH ENDS.