Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/10/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) VERIFY PERMIT AND INSP RECORDS FOR RECENT ELECTRICAL WORK ON PREMISES, THERE ARE TWO SERVICES, NONE IDENTIFIED, MULTIPLE VIOLATIONS ON SITE. POWER ON AT SERVICE EAST BLDG. NO PERMIT PULLED. SERVICE AT WEST END IN VIOLATION OF DEDICATED WORKING SPACE. DOUBLE LUGGING NOT ALLOWED AT MAIN BREAKER, EXPOSED WIRING THRU-OUT, OPEN BOXES, BROKEN OR UNSUPPORTED CONDUIT/WIRING, COVERS MISSING ON BOXES AND SUB-PANEL OUTSIDE BY CAR LIFT NOT OUTDOOR RATED. L-11 LICENSED CONTR. TO MAKE ALL REPAIRS. PERMITS REQUIRED FOR SERVICE UPGRADE AND 1 HOUR GENERAL REPAIR.