Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/10/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) VERIFY PERMIT AND INSP RECORDS FOR RECENT ELECTRICAL WORK ON PREMISES, THERE ARE TWO SERVICES, NONE IDENTIFIED, MULTIPLE VIOLATIONS ON SITE. POWER ON AT SERVICE EAST BLDG. NO PERMIT PULLED. SERVICE AT WEST END IN VIOLATION OF DEDICATED WORKING SPACE. DOUBLE LUGGING NOT ALLOWED AT MAIN BREAKER, EXPOSED WIRING THRU-OUT, OPEN BOXES, BROKEN OR UNSUPPORTED CONDUIT/WIRING, COVERS MISSING ON BOXES AND SUB-PANEL OUTSIDE BY CAR LIFT NOT OUTDOOR RATED. L-11 LICENSED CONTR. TO MAKE ALL REPAIRS. PERMITS REQUIRED FOR SERVICE UPGRADE AND 1 HOUR GENERAL REPAIR. |