Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 02/11/2004 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*/ 1) SERVICE NEEDS AN ADDRESS [PERMANENT - NO MARKER]. 2) DRYER OUTLET NEEDS A NUETRAL AND 30 AMP SP BREAKER GE. 3) SERVICE NEEDS 2 GROUND RODS. 4) TERMINALS ON BREAKER WITH 2 WIRES NEEDS SCREW ONLY 1 WIRE CAN BE ON TERMINAL. 5) OVERHEAD RISER NEEDS A SUPPORT BELOW ROOF. 6) TERMINATE WASHER CIRCUIT TO 20A GE BREAKER. 7) RECEPTACLES BY SINK TO BE GFI. 8) BATH RECEPTACLE TO BE GFI. 9) LIVING ROOM FIXTURE MISSING. 10) SMOKE DETECTORS IN BEDROOMS. |