Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04EL00268

Parcel: 132102650

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
02/11/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*/ 1) SERVICE NEEDS AN ADDRESS [PERMANENT - NO MARKER]. 2) DRYER OUTLET NEEDS A NUETRAL AND 30 AMP SP BREAKER GE. 3) SERVICE NEEDS 2 GROUND RODS. 4) TERMINALS ON BREAKER WITH 2 WIRES NEEDS SCREW ONLY 1 WIRE CAN BE ON TERMINAL. 5) OVERHEAD RISER NEEDS A SUPPORT BELOW ROOF. 6) TERMINATE WASHER CIRCUIT TO 20A GE BREAKER. 7) RECEPTACLES BY SINK TO BE GFI. 8) BATH RECEPTACLE TO BE GFI. 9) LIVING ROOM FIXTURE MISSING. 10) SMOKE DETECTORS IN BEDROOMS.