Permit: T04EL00215

Parcel: 11720019A


Addresses:

181 W BROADWAY BL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/04/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ AT PATIO AREA: 1) EXTENSION CORD CONNECTOR TO BE RAISED TO PREVENT SUBMISSION WHEN WET 2) NEED GFCI PROTECTION AT SOURCE, NEED RAIN TIGHT RECEPTACLE COVER (WHEN IN USE)-ALL AREAS 3) REFRIGERATION-CASE WILL NEED IT'S OWN SINGLE RECEPTACLE AND A WATER SHIELD AT TOP (OPEN WIRING)