Case: T04DV00841

Parcel: 120022280


Addresses:

4420 S 15TH AV

Inspection Status: Correction Required

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
11/01/2004 INSP - INITIAL CODE ENFORCMENT Correction Required VISITED SITE, STRUCTURE WAS FOUND OPENED AND APPEARS RENOVATION OF ENTIRE STRUCTURE IS UNDER WAY. NEW ELECTRICAL DISCONNECTED PANEL W/RISER, NEW ELECTRICAL CIRCUITS INSTALLED THROUGHOUT INTERIOR OF STRUCTURE. DRYWALL HAS BEEN REMOVED FROM CEILING EXPOSING ROOF ASSEMBLY. EVIDENCE OF NEW GAS PIPING AND INSTALLATION OF NEW HOTWATER HEATER TANK. WALKED INTERIOR AND EXTERIOR OF STRUCTURE. SEVERAL BUILDING VIOLATIONS WERE FOUND AND ARE AS FOLLOWS:
ELECTRICAL
1. SEVERAL ELECTRICAL CONDUCTORS HAVE BEEN STRUNG OVER BEAMS AND IN BETWEEN ROOF SHEETING.
2. RISER FOR EMT THOUGH ROOF FOR COOLER DOES NOT HAVE PROTECTIVE GROMMET FOR ELECTRICAL CONDUCTOR PROTECTION.
STRUCTURAL
ROOF ASSEMBLY APPEARS TO HAVE BEEN BUILT BY USE OF UNAPPROVED MATERIALS. MIXED USE OF 4' X 4', 2' X 4', 2' X 6', ALTERATION, ADDITION OF NEW SUPPORT TO STRENGTHEN EXISTING 2 X 4 AND 4 X 4, 2 X 6 HAVE BEEN TOE NAILED AND LACKING APPROVED ATTACHMENT HARDWARE. LARGE AMOUNTS OF TERMITE DAMAGE LUMBER HAVE BEEN SUPPORTED BY ADDITION OF NEW LUMBER. FOUND SEVERAL SECTIONS OF 4 X 4 LUMBER HAD UP TO 6 - 1 1/4 WOOD DOWELS, INSERTED TO FILL HOLES. EXPOSE ENDS HAVE SEVERE WEATHER DAMAGE. WOOD CONTAINS MUCH WOOD ROT. NEW ROOFING PAPER HAS BEEN ISNTALLED OVER DETERIORATED ROOF ASSEMBLY.
WALLS (EXTERIOR)
SEVERAL STRESS CRACKS FOUND THROUGHOUT EXTERIOR OF STRUCTURE. CONVERSATION WITH NEIGHBORS THAT HAVE LIVED NEAR TO STRUCTURE STATE SOME WALL DO NOT HAVE FOOTER. NORTHWALL SHOWS APPROX. 1 1/2" INDENTION.
INTERIOR FEATURES
1. KITCHEN AREA - FLOORING IS A GRADE LEVEL.
2. MIDDLE ROOM CONCRETE SLAB APPEARS TO HAVE BEEN ADDED. MIDDLE OF SLAB BOWS UP.
KITCHEN AREA
WESTWALL CEILING HEIGHT IS AT APPROX. 6' 4" AND DOES NOT MEET CEILING HEIGHT REQUIREMENTS.
PLUMBING
1. ADDITION OF HOT WATER HEATER LACKS TPR DRAIN, B-VENT SYSTEM CLOSET FLANGE HAS BEEN FILLED WITH CONCRETE AND DRAIN FOR SHOWER HAS BEEN COVERED.
3. ALTERATION ADDITION TO ABS SEWER VENT SYSTEM.
WILL TAKE FINDINGS AND PICTURES TO DSD PLAN REVIEW FOR ACCESSMENT APPEARS DRAWINGS WILL BE REQUIRED AS WELL AS NEW ROOF SYSTEM. WILL CHECK ON PLUMBING PERMITS AND GAS PIPING ADDITIONS.