| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2004 | INSP - INITIAL CODE ENFORCMENT | HLOPEZ | Approved | VISITED SITE, STRUCTURE WAS FOUND OPENED AND APPEARS RENOVATION OF ENTIRE STRUCTURE IS UNDER WAY. NEW ELECTRICAL DISCONNECTED PANEL W/RISER, NEW ELECTRICAL CIRCUITS INSTALLED THROUGHOUT INTERIOR OF STRUCTURE. DRYWALL HAS BEEN REMOVED FROM CEILING EXPOSING ROOF ASSEMBLY. EVIDENCE OF NEW GAS PIPING AND INSTALLATION OF NEW HOTWATER HEATER TANK. WALKED INTERIOR AND EXTERIOR OF STRUCTURE. SEVERAL BUILDING VIOLATIONS WERE FOUND AND ARE AS FOLLOWS: ELECTRICAL 1. SEVERAL ELECTRICAL CONDUCTORS HAVE BEEN STRUNG OVER BEAMS AND IN BETWEEN ROOF SHEETING. 2. RISER FOR EMT THOUGH ROOF FOR COOLER DOES NOT HAVE PROTECTIVE GROMMET FOR ELECTRICAL CONDUCTOR PROTECTION. STRUCTURAL ROOF ASSEMBLY APPEARS TO HAVE BEEN BUILT BY USE OF UNAPPROVED MATERIALS. MIXED USE OF 4' X 4', 2' X 4', 2' X 6', ALTERATION, ADDITION OF NEW SUPPORT TO STRENGTHEN EXISTING 2 X 4 AND 4 X 4, 2 X 6 HAVE BEEN TOE NAILED AND LACKING APPROVED ATTACHMENT HARDWARE. LARGE AMOUNTS OF TERMITE DAMAGE LUMBER HAVE BEEN SUPPORTED BY ADDITION OF NEW LUMBER. FOUND SEVERAL SECTIONS OF 4 X 4 LUMBER HAD UP TO 6 - 1 1/4 WOOD DOWELS, INSERTED TO FILL HOLES. EXPOSE ENDS HAVE SEVERE WEATHER DAMAGE. WOOD CONTAINS MUCH WOOD ROT. NEW ROOFING PAPER HAS BEEN ISNTALLED OVER DETERIORATED ROOF ASSEMBLY. WALLS (EXTERIOR) SEVERAL STRESS CRACKS FOUND THROUGHOUT EXTERIOR OF STRUCTURE. CONVERSATION WITH NEIGHBORS THAT HAVE LIVED NEAR TO STRUCTURE STATE SOME WALL DO NOT HAVE FOOTER. NORTHWALL SHOWS APPROX. 1 1/2" INDENTION. INTERIOR FEATURES 1. KITCHEN AREA - FLOORING IS A GRADE LEVEL. 2. MIDDLE ROOM CONCRETE SLAB APPEARS TO HAVE BEEN ADDED. MIDDLE OF SLAB BOWS UP. KITCHEN AREA WESTWALL CEILING HEIGHT IS AT APPROX. 6' 4" AND DOES NOT MEET CEILING HEIGHT REQUIREMENTS. PLUMBING 1. ADDITION OF HOT WATER HEATER LACKS TPR DRAIN, B-VENT SYSTEM CLOSET FLANGE HAS BEEN FILLED WITH CONCRETE AND DRAIN FOR SHOWER HAS BEEN COVERED. 3. ALTERATION ADDITION TO ABS SEWER VENT SYSTEM. WILL TAKE FINDINGS AND PICTURES TO DSD PLAN REVIEW FOR ACCESSMENT APPEARS DRAWINGS WILL BE REQUIRED AS WELL AS NEW ROOF SYSTEM. WILL CHECK ON PLUMBING PERMITS AND GAS PIPING ADDITIONS. |
| 11/17/2004 | INSP - FOLLOW UP CODE ENFORCE | HLOPEZ | Approved | MET ON SITE WITH OWNER & STRUCTURAL ENGINEER. WALKED PROPERTY AT 4420 S, 15TH AVE. STRUCTURAL ENGINEER REQUESTED OWNER TO REMOVE DIRT FROM 3 SEPERATE AREAS FROM BASE OF EXTERIOR WALLS. WEST WALL - REMOVAL OF DIRT PROVED NO FOOTER WAS PROVIDED, REAR SECTION OF STRUCTURE IS SUPPORTED BY CEMENT SLAB ONLY. 2 OTHER HOLES DUG DETERMINED 2 SEPERATE ADDITIONS HAVE BEEN COMBINED. ROOF (EXISTING) ASSEMBLY WILL HAVE TO BE REMOVED. STRUCTURAL ENGINNER WILL SUBMIT FINDINGS TO OWNER & D.N.R. INSPECTOR. WILL DO FW/UP IN 30 DAYS. |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T04DV00841
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
| Date | Name |
| 11/30/2004 | CONTACTED BY PHONE |
| 12/06/2004 | CONTACTED IN PERSON |
| 12/03/2004 | NOTICE OF VIOLATION ISSUED |
| 11/30/2004 | COURT ORDERED ABATEMENT |
| 09/15/2005 | VIOLATION CLOSED |