Case: T04DV00131

Parcel: 11308255B


Addresses:

2940 N TYNDALL AV

Inspection Status: Violation

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
05/24/2004 INSP - INITIAL CODE ENFORCMENT Violation STRUCTURE IN VACANT & SECURED
VISITED SITE, FRONT GATE WAS LOCKED & NO ENTRY TO FRONT DOOR. NO TRESSPASSING SIGNS POSTED ON NORTH SIDE WINDOW. NORTH SIDE OF PROPERTY IS ACCESSABLE FROM APT. COMPLEX ON NORTHSIDE. EXTERIOR VIOLATIONS FOUND.
PLUMBING
(1) HOTWATER TANK LACKING B-VENT SYSTEM & DRAIN FOR TRP VALVE.
STRUCTURAL
(1) DELAPATED & DETERIORATED FRONT PORCH ATTACHED TO MAIN STRUCTURE, PORCH STRUCTURE EXHIBITS SIGNS OF IMENIATE DANGER, EVIDENCED BY LEAGER BOARD COMING AWAY FROM MAIN STRUCTURE. SURPPORT BEAM APPROX. 2 INCH BY 6 INCH IS SAGGING OUT OF PLUMB APPROX 4 INCHES IN A SPAN OF APPROX. 12 FEET.USE OF 2 INCH BY 4 INCH BOARDS USED TO SPAN APPROX. 8 FEET IS EVIDENCE OF IMPROPER INSTALLATION & NO INSPECTION.
WEATHER PROOFING
3 INCH HOLE FOUND ON NORTH WALL OUTSIDE OF KITCHEN.
NUISANCE- ACCUMALATED DEBRIS SUCH AS COIN OPERATED DRYERS & WASHING MACHINES, COUCHES, BED SPRING & OTHER MICS. ITEMS. HAZARDOUS ELECTRICAL
(1) EXPOSED ELECTRICAL CONDUCTORS LACKING PROTECTION AT EAST WALL BY MAIN DISCONNECTS & MISSING BLANKS COVERS. PICTURES WERE TAKEN. NOV TO BE ISSUED AFTER RESEARCH IS DONE. APPROX 2 WEEKS. DO 14 DAY FOLLOW UP.