Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T04CM05435
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/01/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FIRE CAULK AROUND FIRE DAMPER AS NEEDED. PROVIDE REMOVABLE BAND ON FIRE DAMPER FLEX DUCT. WATER HEATER VENT NEEDS MORE CLEARANCE. |
|
04/04/2006 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
01/06/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO SHEETROCK HARD LIDS 2) FIREWRAP ON GREASE DUCT OK 3) PROVIDE REVISION IF ELIMINATING WALL COVERING REQUIRED ON WALL AT TYPE I HOOD |