Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM05435

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/12/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BUILDING
1. PLEASE PROVIDE A LETTER FOR POLE HEAD MAKE UP
06/07/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WE HAVE A MULTI-WIRE DEVICE. A 2-POLE BREAKER IS NEEDED.
2. FINISH PREVIOUS ITEMS.
06/05/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/02/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SPECIAL RECEPTACLES IN KITCHEN TO BE AS OR SINGLE DEDICATED.
2. BOND A/C DISCONNECTS.
3. BOND RACEWAYS AT CONCENTRICS OVER 250 VOLT 250.97
4. PROTECT SEAL TITE FROM SHARP METAL EDGES.
5. MAINTENANCE RECEPTICAL TO BE WITHIN 25' OF UNITS 210.63
6. FILL UNUSED OPENING IN DISCONNECTS.
7. PLEASE LABEL PANEL AS TO WHAT IT OPERATES - GENERAL LABELING NOT ACCEPTABLE.