Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM05435
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/12/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK BUILDING 1. PLEASE PROVIDE A LETTER FOR POLE HEAD MAKE UP |
|
06/07/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WE HAVE A MULTI-WIRE DEVICE. A 2-POLE BREAKER IS NEEDED. 2. FINISH PREVIOUS ITEMS. |
|
06/05/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/02/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SPECIAL RECEPTACLES IN KITCHEN TO BE AS OR SINGLE DEDICATED. 2. BOND A/C DISCONNECTS. 3. BOND RACEWAYS AT CONCENTRICS OVER 250 VOLT 250.97 4. PROTECT SEAL TITE FROM SHARP METAL EDGES. 5. MAINTENANCE RECEPTICAL TO BE WITHIN 25' OF UNITS 210.63 6. FILL UNUSED OPENING IN DISCONNECTS. 7. PLEASE LABEL PANEL AS TO WHAT IT OPERATES - GENERAL LABELING NOT ACCEPTABLE. |