Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
Permit Number - T04CM05435
Inspection Description - ELECTRIC - OUTDOOR LIGHTING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2006 | ELECTRIC - OUTDOOR LIGHTING | Approved | IVRS - Inspection :* | |
04/04/2006 | ELECTRIC - OUTDOOR LIGHTING | Partial Approval | IVRS - Inspection :* 1. IF SUPPORTING FIXTURE WHIPS THEY ARE TO BE AS PER 300.11 2. SECURE FIXTURES TO GRID 410.16 3. SUPPORT WIRES FOR BOXES IN GRID 4. IF MANUFACTURERS CLIPS ARE USED THEY MUST BE EFFECTIVE. 5. PLEASE PROVIDE RECORD & READINGS FOR GFCI TESTING 6. BOND JUMPERS TO BE SIZED PER 350.102 & 250.66 LINE SIZE 7. LABEL DISCONNECTS 8. NO FUSES AT THIS TIME 9. BOND JUMPER TO BE SIZED PER 250.102 & 250.122 LOAD SIDE 10. PLEASE TERMINATE ALL STRANDS OF CONDUCTORS. |
|
03/27/2006 | ELECTRIC - OUTDOOR LIGHTING | Partial Approval | IVRS - Inspection :* OK POLE TO POLE 3/4" PVC OK 3/4" PVC FIRE RISER TO WITHIN 10' OF BLDG. 1. CONDUITS AT BUILDING TO BE AT DEPTHS PER 300.5 |
|
03/14/2006 | ELECTRIC - OUTDOOR LIGHTING | Partial Approval | IVRS - Inspection :* OK 2 POLE BASES |
|
03/07/2006 | ELECTRIC - OUTDOOR LIGHTING | Partial Approval | IVRS - Inspection :* OK 2 POLE BASES |