Permit: T04CM05412

Parcel: 140324360

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T04CM05412

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
03/18/2005 FRAMING Approved IVRS - Inspection :*
03/17/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRIC WIRE DAMAGED BY STUD SHOE BY 90 IN GARAGE 1/2 HOT
2) NO DWV WATER TEST
3) FIRE STOP CHASE AT TUB/SHOWER
4) WIRE OUT OF CEILING BEDROOM 3
5) STUD SHOES NOT PROPERLY NAILED
03/10/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPLACE OVERBORED STUDS AT GARAGE SHEAR WALL
2) NO TEST ON DWV'S
3) FLEX DUCT RESTRICTING ATTIC ACCESS
4) ROMEX CUT AT LAUNDRY FIXTURE BOX
5) FIRE BLOCK MISSING AT HALL BATH
6) CALL INLATH AT INTERMEDIATES
7) STOPPED INSPECTION