Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/16/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*NOT READY PER TONY | |
| 12/15/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*UNIT DOES NOT RUN PROVIDE COMMON TRIP BREAKER TO DISCONNECT IN PANEL, TERMINATE EQUIPMENT GROUND TO GROUND TERMINAL SECTION INSTEAD OF LUG ( NO SOLID STRANDED MIX) DO A BETTER JOB OF IDENTIFYING NEW EQUIPMENT @ PANEL. AT DISCONNECT-MAKE SURE OF PROPER FUSE SIZE PIG TAIL GROUND INTO LUG ( DON'T SHARE) AND WHERE DOES SECOND LEG TERMINATED IN UNIT? ( OPEN UNIT FOR INSPECTION) |