Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
01/20/2005 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
12/15/2004 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*/1)PAHD 22'S ARE MISSING 2)LIVE END OF TENDONS MAY NOT BE DEFLECTED BY SOIL OUTSIDE OF EXCAVATIONS 3)TENDONS IN SLAB ON GRADE MUST BE FLAT PROFILE (EXCEPT @TURN DOWN REV PLAN) 4)RELOCATE TENDONS UP TO 6" T0 AVOID SLAB PENETRATIONS 5)HAVE SPECIAL INSP REPORT @ SITE WITH PLANS PLEASE. 6)OK TO PLACE CONCRETE WHEN SPECIAL INSPECTOR CONFIRMS REPAIRS