Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/23/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)BACKDRAFT DAMPERS ON DRYER VENTS DO NOT OPEN. CLEAN OUT DEBRIS & ANY STAPLES FROM LATH BLOCKING FLAPPERS. 2)MARK UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY 3)PROVIDE SCREENS IN ALL T-TOPS ON ROOF 4)PROVIDE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES THE ROOF 5)PAINT PVC DRAINS ON ROOF W/LATEX PAINT 6)INSTALL FREASH AIR INTAKES |