Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2005 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 02/23/2005 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UFER NEEDS TO BE CONNECTED DIRECTLY TO NEUTRAL BUS AT SERVICE NOT AT TEH EQUIP. GROUNDING BUS BAR 2) HANDY BOX IS TOO SMALL FOR 5 #4 CONDUCTORS AND AN OUTLET 3) SECURE N.M CABLE AT PANEL WITHIN 12" OF PANEL MIN .4) STAPLE PULLED LOOSE AT S. EAST ? AT EAST WALL 5) BRING BOX OUT FURTHER @ PANTRY SWITCH. 6) PER TEP METAL ADDRESS REQUIRED AT BOTH METER BASES 7) PLANS NOT ON SITE. 8) SECURE N.M PER NEC -IRC. 9) FHA PLATES NEEDED AT A FEW LOCATIONS 10) INSTALL J-BOX FOR BATH LIGHT BAR. |