Permit: T04CM04846

Parcel: 140291960

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
05/17/2007 FIRE - ALARM FINAL Approved
05/16/2007 FIRE - ALARM FINAL Denied Alarm system did not knowledge all alarms you needed to push the knowledge button to see what part of the system set off alarm.

While testing the alarm for the Kitchen hood system it was noticed by silencing the alarm at the fire alarm panel the hood electrical system for the hood appliances came back on. The only way to reset appliances is by resetting the Ansul system by a licensed hood extinguisher system tech and not by pushing a silencing button or reset button at the fire alarm panel.