Permit: T04CM04846

Parcel: 140291960

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
05/03/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1. ROOFTOP PKG. UNITS GAS PIPING OK
OK FOR GAS CARD
2. KITCHEN, GREASE DUCT FIRE WRAP OK
EX. BLOWER DUCT
NEEDS TO BE PAINTED, ROOFTOP
3. COMPLETE PROPER SIZE FUSING WHERE NECESSARY
4. KITCHEN GRID OK TO COVER
04/30/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CONTINUE FIRE WRAP UP ABOVE WOOD CURB
2. COMPLETE ACCESS PANELS
04/19/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CHECKED CLASSROOMS BOTH SIDES OF N.E CORRIDOR
OK TO FIRE WRAP GREASE DUCT
04/12/2007 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
3:35 PM NO SUPER ON SITE
COULD NOT LOCATE PLANS OR AREA TO INSPECT
04/11/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
WELDS ON GREASE DUCT LEAKING.
04/04/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES MIDDLE CLASSROOM AREA
DISCUSSED TYPE 1 ACCESS/CLEANOUTS
03/27/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES N.W WING CLASSROOMS
03/22/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO MOUNT DUCT SMOKE DETECTORS INSIDE UNITS AS LONG AS SENSING TUBES PASS THROUGH THE AIRFLOW & ARE ACCESSIBLE.