Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1. ROOFTOP PKG. UNITS GAS PIPING OK OK FOR GAS CARD 2. KITCHEN, GREASE DUCT FIRE WRAP OK EX. BLOWER DUCT NEEDS TO BE PAINTED, ROOFTOP 3. COMPLETE PROPER SIZE FUSING WHERE NECESSARY 4. KITCHEN GRID OK TO COVER |
|
| 04/30/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CONTINUE FIRE WRAP UP ABOVE WOOD CURB 2. COMPLETE ACCESS PANELS |
|
| 04/19/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CHECKED CLASSROOMS BOTH SIDES OF N.E CORRIDOR OK TO FIRE WRAP GREASE DUCT |
|
| 04/12/2007 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 3:35 PM NO SUPER ON SITE COULD NOT LOCATE PLANS OR AREA TO INSPECT |
|
| 04/11/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* WELDS ON GREASE DUCT LEAKING. |
|
| 04/04/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES MIDDLE CLASSROOM AREA DISCUSSED TYPE 1 ACCESS/CLEANOUTS |
|
| 03/27/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES N.W WING CLASSROOMS |
|
| 03/22/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO MOUNT DUCT SMOKE DETECTORS INSIDE UNITS AS LONG AS SENSING TUBES PASS THROUGH THE AIRFLOW & ARE ACCESSIBLE. |