Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2007 | ELECTRIC - ABOVE CEILING | Approved | ||
| 04/30/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK FOR TCO FOR FURNITURE 2. BE ADVISED KITCHEN RECEPTS (110V) TO BE GFI PROTECTED PER 210.8 NEC |
|
| 04/17/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 03/21/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK WEST & NORTH CLASSROOMS 2. INSTALL BOND BUSHING FOR AC DISCONNECT TERMINATIONS 3. LOAD WIRING FROM DISCONNECT TO WIRING COMPARTMENT MUST BE IN CONDUIT. |
|
| 12/22/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CONDUITS UNDER ROOF DECK -- ID OR CUT LOCATIONS FOR J-BOXES |