Permit: T04CM04523

Parcel: 140420760

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
09/09/2005 MECHANICAL - INTERMEDIATE Approved
07/01/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) TERMINATE SECONDARY DRAINS THRU CEILING LABEL FAN COILS
2) 2ND FLOOR SOUTH SIDE CHECKED CONDENSATE DRAIN LINES, DUCT AND DIFFUSERS
3) DUCT SMOKE DETECTORS TO BE INSTALLED IN THE RETURN AIR DUCTS
4) OK FOR CEILING TILES-LEAVE OUT UNDER EACH DETECTOR
03/21/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :* 1) A/H WARM STATION- RELOCATE SPRINKLER LINE OR AIR HANDLER!. 2) CH. ALL REFRIG DOPPER LINES FROM STEEL 1ST FLR. REST ROOMS/ JANITOR CLOSET ALL ABOVE HARD LID
02/24/2005 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*