Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) SOIL WATER TEST IS OK 2) OVERHEAD WATER DISTRIBUTION TEST IS OK 3) NOTE: SHALL PROVIDE SPECIALTY COUPLINGS WHERE ABS DWV CONNECTS TO CAST IRON |
|
| 03/18/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 1ST FLOOR RESTROOMS, JANITORS RM AND WARMING ROOM OVERHEAD WATER DISTRIBUTION IS OK. | |
| 03/09/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SOIL WATER TEST FOR DWV SYSTEM IS OK. 2) DWV SYTEM IS COMPLETE | |
| 12/29/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/WATER TEST WSTE & VENT FROM 4" DRAIN OVERHEAD 1ST FLOOR UP THRU SHOWER 245, MENS RESTROOM 246, WOMENS REST ROOM STOOL AREA (ONLY) 248, JANITOR 247 UP TO 3" UNIT AT FUTURE 4" THRU ROOF OK | |
| 12/14/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PLEASE HAVE 03005 ROUGH SOIL ADDED TO PERMIT. 3" BUILDING DRAIN FROM POINT OF CONNECTION TO MAIN BUILDING DRAIN & 7-8 +F TO FLOOR SINK IN EQUIP #123 10' ABOVE FINISH FLOOR WATER TEST |