Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/24/2005 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection :* |
| 01/20/2005 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection :1) P-6 HAS 180 DEGREE OF CHANGE OF HORIZONTAL DIRECTION SHALL PROVIDE A FLOOR C.O @ LOCATION WHETER DRAIN EXCEEDS 135 DEGREES. 2) VENT FOR FLOOR DRAIN OUTLET CANNOT BE BELOW TRAP ACM @ RM# 106. 3) OK TO BACKFILL ALL OTHER AREAS 4) RETEST SYSTEM. |