Permit: T04CM04523

Parcel: 140420760

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/01/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/07/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* OK OFFICES NORTH OF EXPANSION JOINT 2ND FLOOR.
06/01/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) DO NOT USE CEILING WIRES TO SUPPORT CABELING THAT IS INTENED TO SUPPORT GRID
2) COMPLETE MAKE ? TO REVISE
05/04/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) NOTE: FOR TEMP POWER FOR TEST, NEED LETTER OF TORQUE GFCI MAIN BREAKER TEST-COPY, NEED TO VERIFY BLDG, STEEL AND WATER PIPE BONDING. BOND FOR TEMP POWER FOR TEST. OK GROUNDING AT SERVICE-2 GROUND RODS
2) OK ABOVE CEILING FOR ROOMS 237, 235, 240 AND 230 2ND FLOOR
04/15/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* NORTH & CENTER GLASS BLOCK TURETS OK TO COVER
04/11/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*OK SOUTH GLASS BLOCK TURETS, EXCEPT NORTH-EM BALLAST & J BOXES MUST BE ACCESSIBLE
04/01/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* OK RESTROOM HARD LIDS 1ST & 2ND FLOOR
03/31/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* 1) SUPPORT MC IN RESTROOM 2ND FLOOR. 2) OK HARD LIDS HALLWAY, RESTROOMS, JANITORS CLOSET