Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/07/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK OFFICES NORTH OF EXPANSION JOINT 2ND FLOOR. | |
| 06/01/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) DO NOT USE CEILING WIRES TO SUPPORT CABELING THAT IS INTENED TO SUPPORT GRID 2) COMPLETE MAKE ? TO REVISE |
|
| 05/04/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) NOTE: FOR TEMP POWER FOR TEST, NEED LETTER OF TORQUE GFCI MAIN BREAKER TEST-COPY, NEED TO VERIFY BLDG, STEEL AND WATER PIPE BONDING. BOND FOR TEMP POWER FOR TEST. OK GROUNDING AT SERVICE-2 GROUND RODS 2) OK ABOVE CEILING FOR ROOMS 237, 235, 240 AND 230 2ND FLOOR |
|
| 04/15/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* NORTH & CENTER GLASS BLOCK TURETS OK TO COVER | |
| 04/11/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*OK SOUTH GLASS BLOCK TURETS, EXCEPT NORTH-EM BALLAST & J BOXES MUST BE ACCESSIBLE | |
| 04/01/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK RESTROOM HARD LIDS 1ST & 2ND FLOOR | |