Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/03/2004 | FRAMING | Partial Approval | IVRS - Inspection :*/ 1) WATER HEATER "B" VENT REQUIRES 1" CLEARANCE TO COMBUSTIBLE MATERIAL 2) ALL ELECTRICAL OUTLETS ARE UNDERGROUNDED. REMOVE ALL COVERS AND DEVICES FOR INSPECTION OF WIRING ALL 120 VOLT CIRCUITS MUST BE 2 WIRE CROSS GROUND 3) PROVIDE 100 SQUARE INCHES COMBUSTION AIR WITHIN 1' OF CEILING AND 100 SQUARE INCHES COMBUSTION AIR WITHIN 12" OF FLOOR FOR GAS WATER HEATER 4) SECURE GAS LINE SO NO MOTION EXISTS 5) WATER HEATER T & P LINE CANNOT HAVE CORRIGATED TUBING 6) DRYER MUST BE ON A 4 WIRE CIRCUIT, 2 HOT 1 GROUND AND 1 NEUTRAL WITH 4 WIRE OUTLET AND PIG TALE 7) INCORRECT METAL BOXES USED OUTSIDE 8) SUPPORT PLASTIC CONDUIT AT 4' ON CENTER 9) WASHER DRAIN MUST BE 2" WITH A "P" TRAP |