Permit: T04CM03825

Parcel: 129130040


Addresses:

926 E SILVERLAKE RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/14/2007 ELECTRIC - FINAL Approved
01/17/2007 ELECTRIC - FINAL Denied 1. SUPPORT MC CABLE TO RECEPT ON LEFT OF PANEL INSIDE
2. BUSHING REQUIRED AT FEEDER CONDUIT TERM. INTO PANEL.
3. REMOVE BAR BETWEEN NEUTRAL & GROUND BARS - INSIDE - NEUTRAL SHOULD ONLY BE BONDED AT SERVICE, REMOVE GREEN SCREW AT NEUTRAL BAR.
4. SUPPORT EMT & RECEPTACLE BOXES PER CODE
07/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
BLD. LOCKED -- RECALL INSPECTION