Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2007 | ELECTRIC - FINAL | Approved | ||
| 01/17/2007 | ELECTRIC - FINAL | Denied | 1. SUPPORT MC CABLE TO RECEPT ON LEFT OF PANEL INSIDE 2. BUSHING REQUIRED AT FEEDER CONDUIT TERM. INTO PANEL. 3. REMOVE BAR BETWEEN NEUTRAL & GROUND BARS - INSIDE - NEUTRAL SHOULD ONLY BE BONDED AT SERVICE, REMOVE GREEN SCREW AT NEUTRAL BAR. 4. SUPPORT EMT & RECEPTACLE BOXES PER CODE |
|
| 07/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* BLD. LOCKED -- RECALL INSPECTION |