Permit: T04CM03716

Parcel: 138240850

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/30/2005 MECHANICAL - ABOVE CEILING Approved
08/08/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) WHERE ARE SECONDARY OVERFLOW COND. LINES ?
2) A/C OVER BREAK ROOM RELOCATE SUPPLY TOP. BLOCKING ACCESS TO AIR HANDLER
3) ID AIR HANDLER WITH NUMBER AND COMPLETE DATA PLATES, AUX HT YES ? MARK IT NOW, NO ?
06/23/2005 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* SUPPLY/RETURN HARD DUCT JOINTS NEED TO BE SEALED. NOTE: MAINTAIN CLEAR ACCESS TO FRONT OF SUSPENDED FAN COILS. 1) OVERFLOW PANS UNDER EVAP COILS?