Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/08/2006 | ELECTRIC - FINAL | Cancelled | CANCELLED PER | |
| 02/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 12/21/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BONDING JUMPER ACCROSS NON METALLIC A/C BELOW ROOF MECH 2) A/C NOT ON PLANS AND/OR ELECTRIC CALCULATIONS 3) INSTALL COVER PLATES RECEPTACLES SWITCHES ETC... 4) INSTALL LIGHT FIXTURE 5) POST ADDRESS NUMBERS ON HOUSE JACUZZI 6) RAISE PLUMBING VENTS ABOVE A/C UNIT FOR PROPER VENTING AND MECH VENT ALSO 7) KITCHEN COUNTER TOP RECEPTACLES NOT TO CODE 8) RAISE FLU PIPE 12" ABOVE PARAPET 9) INSTALL GAS AND H20 BONDS 10) MUST COMPLETE AND CALL IN ALL TRADES FOR FINALS 11) INSTALL STOOP 12) INSTALLL SAN-TEE AT VENT AND REDUCER TO TIE CONDENSATE DRAIN INTO ROOF VENT PIPE AND INSTALL TRAP ALSO 13) MUST COMPLETE ALL TRADES THEN RECALL ALL 14) STOPPED INSPECTION |