Permit: T04CM03666

Parcel: 136384460

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/15/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
08/25/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/PARTIAL-WATER TEST WASTE & VENT UNDERGROUND ONLY (PARTIAL) PENDING VERIFICATION FROM ENGNIEER FOR MANHOLE DEING HIGHER THAN FLOOD ROM OF ALL FIXTURES IN BCD, SO BACKWATER INSTALLATION IS REQUIRED>
1) BACKWATER VALVES TO BE EXTENDED TO GRADE IF REQUIRD
2) PROVIDE CERTIFICATE OF CONFORMANCE FROM PIMA COUNTY ADEQ FOR SITE SEWER INSTALLATION AND VERIFICATION OF INSPECTION OF SITE SEWER.
3) 03055-SEWER HCS CONNECTION TO BE CALLED IN AND CORRECT TRANSITION GLUE OR APPROVED COUPLING SHALL BE USED AT THIS LOCATION.