Permit: T04CM03526

Parcel: 13811045A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
12/31/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :* 1) SOIL WATER TEST IS OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) GAS PRESSURE TEST IS OK 4) OK FOR DRY WALL
12/30/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)GAS PRESSURE TEST OK 2)C.O. FOR KITCHEN SINKS MUST BE LOCATED IN A VERTICAL POSITION. TRAP ARMS FOR KITCHEN SINK SHALL BE MIN. 1 1/2 ALL THE WAY OR MAX 2" ALL THE WAY FROM BARREL TO TRAP 3)RE TEST SYSTEM