Inspection Status: Denied

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
03/10/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STRAP HEADERS AT BEARING
2) NEED ELECTRIC SERVICE INCREASE ON CARD
3) RELOCATION OF H20 HEATER, RANGE, ALL WATER PIPING AND EXHAUST HOOD KITCHEN ISLAND
4) INSTALL 1" RISER AT METER
5) SUBMIT REVISED GAS PLANS FOR APPROVAL (SIZE OF PIPING LENGTH OF RUN AND APPLIANCES)
6) MUST PRIME AND WRAP ALL UNCOATED SCOTCH KOTE GAS PIPING
7) INSTALL GAS COCK BEFORE UNION EXTERIOR
8) OPEN UP WALLS TO EXPOSE ALL ELECTRIC ON PLAN (FRONT ENTRY FRAMING ONLY
9) PLAN SHOWS RIGHT AND LEFT ELEVATIONS 4' OPENINGS FRONT ENTRY (6' EXISTS) AND PARAPET TO STOP ON NORTH SIDE BEFORE PEAK EXISTING ROOF
10) PLAN CALLS FOR NEW 3 1/8" X 10 1/8" GLU LAM BEAM
11) NEED TO EXPOSE BACKSIDE OF LEDGERS TO VERITY A35'S
12) NEED TO EXPOSE PARAPET WALL TO VERIFY BOTTOM PLATE ATTACHMENT TO EXISTING
13) BOTTOM WOOD PLATES TO HAVE FULL BERAING ON CONCRETE AND INSTALL PLATE BOLTS MINIMUM 2 BOLTS PER PLATE 1/2" DIAMETER