Inspection Status: Not ready for Inspection

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
04/26/2005 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
1) ELECTRIC INSIDE ENTRY WAY TO BE IN BOX AND SECURE
2) REPLACE DAMAGED WIRES SAME LOCATION
3) UNABLE TO VERIFY EXISTING ELECTRIC GROUNDING WILL NEED TO DRIVE 2 8' GROUND RODS MINIMUM 6' APART
4) REAR PORCH SLAB POURED WITHOUT INSPECTION APPROVAL, EXPOSE CONCRETE FTGS AT POST BASES
02/09/2005 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) NEW COVERED ENTRY AND NEW BAY WINDOW (WESTSIDE)
2) OK TO POUR
01/31/2005 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
FOOTINGS INCOMP SEE PLANS AND COMPLY