Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T04CM03253
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/14/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :SUBJECT TO APPROVAL OF 125A FEEDERS INSTEAD OF 200A | |
| 10/12/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PLAN STATES ON ELECTRICAL SHEET-ALUM WIRE NOT TO BE USED-PANEL FEEDER IS ALUM SO ARE 2 OTHER CIRCUITS IN PANEL 2)ROMEX FITTINGS ON TOP OF PANEL LOOSE 3)INSTALL FLEX ON WATER HEATER AT WALL AND NAIL TO STUD. 4)1/O AL FEEDER OK FOR 125AMPS PLAN SHOWS 200A PANEL & 200A FEEDER, |