Permit: T04CM03253

Parcel: 13816024A


Addresses:

331 E ELVIRA RD #01


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T04CM03253

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/03/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/14/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :SUBJECT TO APPROVAL OF 125A FEEDERS INSTEAD OF 200A
10/12/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)PLAN STATES ON ELECTRICAL SHEET-ALUM WIRE NOT TO BE USED-PANEL FEEDER IS ALUM SO ARE 2 OTHER CIRCUITS IN PANEL 2)ROMEX FITTINGS ON TOP OF PANEL LOOSE 3)INSTALL FLEX ON WATER HEATER AT WALL AND NAIL TO STUD. 4)1/O AL FEEDER OK FOR 125AMPS PLAN SHOWS 200A PANEL & 200A FEEDER,