Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CORRECTIONS IN PROGRESS |
|
| 08/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* UNIT #1 INSTALL SMOKE DETECTORS PER INSTALLATION INSTRUCTIONS PROVIDE WITH DETECTORS FROM MANUFACTURER - NEC 110.3 #2 SAME AS ABOVE/INSTALL SMOKE DETECTORS IN REQUIRED LOCATION. #3 INSTALL SMOKE DETECTOR CORRECTLY - KITCHEN COUNTER CKT NOT ALLOWED TO HAVE LIGHTING LOAD ON IT - NEC 210.52(B)(2) - MULTI-WIRE BRANCH CKT TO KITCHEN NEEDS TO BE ON SEPARATE PHASES - NEC 210 #4 FINISH ALL CORRECTIONS FROM PREVIOUS INSPECTION. |
|
| 08/01/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL ALL COVER SCREWS IN SERVICE COVERS 2. COMPLETE HOUSE LIGHTING 3. IN AC DISCONNECTS - CAN'T RUN STAT WIRE IN DISCONNECTS AND SEAL UNUSED OPENINGS, ALSO PROVIDE PROPER CONNECTOR ENTERING DISCONNECT FOR CONDUCTORS. 4. MAX 15 AMP. ON 14 GAU. WIRE 5. 20 AMP. MIN FOR BATH GFI 6. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED 7. PROVIDE DISCONNECT FOR WATER HEATERS 8. HAVE SWITCHES MOUNTED UPSIDE DOWN 9. SMOKE DETECTORS NEED ARC FAULT PROTECTION IN BEDROOMS AND PROVIDE INSTALLATION INSTRUCTIONS. 10. KITCHEN COUNTER CKT'S TO HAVE NO OTHER LOADS. INSPECTION FOR UNIT #4 ONLY -- CHECK FOR THESE AND OTHER PROBLEMS IN ALL UNITS. |
|
| 06/26/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |