Permit: T04CM03185

Parcel: 122173100

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/14/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/20/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK OUTDOOR HOUSE LIGHTING
12/08/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ADD SMOKE DETECTOR IN EACH UPSTAIRS HALLWAY
2) OK TO COVER ELECTRICAL AFTER SMOKE DETECTORS INSTALLED
3) BOND GAS AND WATER TO SERVICE
12/06/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*ALL UNITS
ONLY 1 NEUTRAL PER SCREW IN SUB PANEL
HAVE 12 GA?/AND 14 GAL WIRE ON SMOKE DET. RUN? ( 15 AMP MAX) AND 3 WAY CKT'S
MAKE SURE ALL ROMEX SHEATHING ENTERS PANEL/BOX'S
BATH CKT'S TO BE ON OWN CKT'S OR DONT LEAVE BATH'S ( GFI)
INSTALL ADDITIONAL NAIL PLATED AS NEEDED
IF CEILING FANS ARE INSTALLED, USE FAN RATED BOX'S